Power Cycling Issues @ Closed Die Forging Press
Overview
My company had recently commissioned a closed-die press. I was originally sent to site to install a remote connection device (a Netbiter).

While on site, the customer reported continuous crashes that forced them to cycle power to the entire press, sometimes 15 times a day, causing a great loss of productivity.
Task
I wasn't tasked with solving this, but took it upon myself to help: diagnose the reason for the crashes and fix it.

My work
- Confirmed the reported fault was occurring by analysing data from the remote connection device.
- Found the cause by analysing the PLC diagnostics buffer.
- Changed the safety settings on the Siemens safety cards to allow more time for input detection.
- Improved the HMI design to fix operator complaints around motor starting.
- Wrote a detailed report of the proposed resolutions.

The holdup valve discrepancy time was changed from 50 ms to 200 ms, giving the switch more time to change state and greatly reducing false flags. All other safety discrepancy times were also increased to 200 ms. Three error-handling blocks were added to the program to stop the PLC freezing when a fault is found.

Outcome
Maintenance staff and management were happy after the visit, and the follow-up work uncovered a serious fault with an easy fix.